ver 0.4.1b
01 Aug 06


Barometric pressure based on:

Elevation
Pressure (psia)
Pressure (In. Hga.)

Enter value: 
Humidity measured as:

RH (%)
Wet Bulb (oF)
Dew Point (oF)
I want to find:

Process Loads
Air Flow
Conditions entering process
Conditions leaving process

(Under construction)

Calculate ADP & Bf

 Include Fan Heat





ENTERING

CFM:
Temperature:
Humidity:


                             Btuh        Tons
  Sensible Load:
      Latent Load:
System Schematic
Condensate: lbs/hr
                   Fan Heat: Btuh/1000 cfm
           Bf:  %
      ADP:  F
 GSHF: 
              





LEAVING

CFM
Temperature
Humidity




Barometric Pressure(psia) 


Air Condition Entering System
Dry
Bulb
(oF)
Wet
Bulb
(oF)
Dew
Point
(oF)
Enthalpy
(Btu/lb)
Relative
Humidity
(%)
Humidity
Ratio
(lb H2O/lb da)
Specific
Volume
(lb/cf)


Air Condition
Dry
Bulb
(oF)
Wet
Bulb
(oF)
Dew
Point
(oF)
Enthalpy
(Btu/lb)
Relative
Humidity
(%)
Humidity
Ratio
(lb H2O/lb da)
Specific
Volume
(lb/cf)

Air Condition Leaving System
Dry
Bulb
(oF)
Wet
Bulb
(oF)
Dew
Point
(oF)
Enthalpy
(Btu/lb)
Relative
Humidity
(%)
Humidity
Ratio
(lb H2O/lb da)
Specific
Volume
(lb/cf)

For additional thermodynamic properties of the above conditions, click on the button next to the properties you wish to expand.

INTERPRETING PROGRAM MESSAGES

ADP Message Box

Valid Coil Process - The coil process line resulting from your data crosses the saturation curve.  The process is possible.  It may or may not be appropriate for your application.

Invalid Coil Process - The coil process line resulting from your data does not cross the saturation curve.  The process is impossible.  This is probably due to a very high latent load.  This does not imply you cannot achieve your desired leaving air conditions.  However, you will need to revise your system design to do so.

Impractical Coil Process - Either the ADP is lower than 48 oF or the bypass factor is less than 5%.  An ADP of 48 oF is considered by many to be the lowest economical ADP for comfort cooling conditions.  The 5% lower limit on bypass factor is arbitrary, but is generally obtainable only with a deep coil.  Consult your manufacturer's specifications to determine what is available.  For all practical purposes, a bypass factor of 0% may be considered impossible.

Primary Message Box

Leaving Air Conditions Modified - This message can only occur when a fan heat calculation is desired and you've specified a draw through supply fan.  Regardless of whether or not you include fan heat in your calculations, the entering conditions represent those air conditions leaving the return fan and entering a blow through supply fan (if your fan is blow thru).  Likewise, the leaving conditions are those conditions leaving the a draw through supply fan (if your fan is draw thru) and being supplied to the distribution duct work, not to the space.  (Did you remember to account for duct heat gains?)  When you ask for fan heat to be included and your fan is a draw through fan, the program calculates a temperature change across the fan and subtracts that from your desired leaving air condition resulting in an off-coil condition necessary to achieve your desired supply condition after the fan.  If your desired condition has a very high dew point, then it is mathematically possible for the dry bulb to be numerically less than the dew point coming off the coil.  Obviously, this is cannot happen.  Under this condition, the off-coil dry bulb temperature is raised to equal the dew point of your specified leaving air condition and the air temperature leaving the fan is recalculated.  This also results in the aforementioned message in the ADP Message Box of 'Impractical Coil Process' since the bypass factor required to do this is 0%.

Entering conditions are outside the scope of ANSI/ASHRAE 41.6-1994 - Although based on the papers of Goff and Gratch and of Hyland and Wexler, this standard does simplify the complex psychrometric formulas defined by these researchers.  Since the formulas are simplified, there may be some error in extreme conditions.  Thus limits are provided within the standard.  These limits are incorporated into this program.  This message indicates your input data will not provide reliable output when calculation via this standard.  Given normal comfort cooling conditions as well as an arbitrary limit imposed on the input data, it is unlikely you will ever see this message.

Results are within the scope of ANSI/ASHRAE 41.6-1994 - This message indicates your input data yielded results that fell within the parameters of this standard as briefly explained above.  This message should not be construed as a validation of your design.

Entering/Leaving Wet bulb is to low for stated dry bulb - if you look at a psychrometric chart, you will see that at any dry bulb temperature with 0% relative humidity, there is a corresponding wet bulb temperature.  Since the air is devoid of water at 0% relative humidity, this wet bulb is the lowest possible condition attained.  This message means you have entered a wet bulb below this value.  Mathematically, this would result in a negative value of relative humidity.

The following messages are related to faulty input and are self explanatory.

     Entering/Leaving Wet bulb cannot exceed dry bulb
     Entering/Leaving Dew point cannot exceed dry bulb
     Entering/Leaving Relative humidity must be between 0% and 100% inclusive


Disclaimer and Copyright Information

Program Release History